146
Automatic filling unit

AUTOMATIC FILLING UNIT
IT IS INSTALLED TO MAINTAIN THE HEATING SYSTEM PRESSURE STABLE AT A SET VALUE, AUTOMATICALLY TOPPING UP WITH WATER, AS REQUIRED

Equipped with shut-off valve, stainless steel filter and check valve.
Piston operation.
Body in brass.
Minimum and maximum working temperature: 0°C, 80°C.
Maximum inlet pressure: 16 bar.
Outlet pressure can be adjusted between 0,5 and 4 bar
Factory preset: 1,5 bar. 
Pressure gauge threaded connection 1/4”.
Pressure gauge: scale (0-6) bar.
Threads: ISO 228 (equivalent to DIN EN ISO 228 and BS EN ISO 228).
Mention “1460012SM” in the code only to receive item without pressure gauge.

SizePressureCodePackingSTEP
1/2" (DN 15)16bar/232psi14600121/12
1/2" (DN 15)16bar/232psi1460012SM1/22

Range AUTOMATIC FILLING UNIT